General technical data - Reactors for Detuned Filter Circuits

rated power QL5 ... 100 kVAr
rated voltage UR230 / 400 / 415 / 440 V
frequency fR50 / 60 Hz
detuning degree p(standard)5,67 / 7 / 8 / 12,5 / 14 %
designiron core, two air gaps, vacuum resin impregnation
protection degreeIP 00
insulation classT 40 E
coolingnatural cooling
standardsVDE 0550 / 0532, IEC 76
terminationsterminal blocks or copper lugs
basis insulation level
(winding to core)
3,0 kV
tolerance of inductance±3%
fundamental harmonic loadI1 = 1.06 IR
(IR = fundamental harmonic current of the detuned capacitor)
propotion of harmonics
(operational period = 100%)
U3 = 0.5% UR
U5 = 5.0% UR
U7 = 5.0% UR
(different propotions on request)
thermal dataIth = 1.05 Ieff
Ith = 1.168 IR
magnetic loadIlin = 1.2 (I1 + I5 + I7)
Ilin = 1.8 IR (with L>=0.95 LR)

For further information please order our data sheets.

(enquiry form)

Home